FOCVT | SV80 | ТОР300 | ||||||||||||||||||||||||||
|
|
|
||||||||||||||||||||||||||
Description | ||||||||||||||||||||||||||||
1.Test Results1.1. IEC 61850-9-2LE Stream Publishing by FOCVT Electronic ModuleFOCVT publishes 9-2LE stream with 80 samples per cycle. Stream successfully received by SVScout (Omicron). No errors detected. 1.2. CID File Generation by FOCVT Electronic ModuleSoftware Tool provided by Profotech with FOCVT successfully generated CID (Configured IED Description) in accordance with present configuration. CID file validated via www.61850.com. No errors detected. 1.3. Configuration of TOP300 Relay by IC Bresler via CID FileSoftware Tool for configuration of TOP300 relay series successfully loads CID file, generated by Profotech sofware and configures subscription in accorance with CID-file provided. No errors detected. 1.4. Reception of IEC 61850-9-2LE stream by TOP300 IEDTOP300 IED provided by IC Bresler successfully receives digital data stream published by FOCVT and displays RMS current and voltage measurements correctly. No errors detected. Table 1. Test Results.
 |